Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 24
1912XR Installation Guide
26.3 Multiple Indicating circuit modules for zoned annunciation
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
24 VDC 5 Amp
Maximum
Power Supply
Trouble Contacts
N/C
Zone 2 Indicating Circuit
Module.
DMP Model 866
37mA at 12 VDC
The Auxiliary Power Supply and Indicating
Circuit Module trouble contact Loop must
be programmed as a Supervisory Type Loop
and must be selected for display in the
keypad status list.
See section 10.6 in the 1912XR
Programming Manual (LT-0171).
NOTE: If an auxiliary supply is
not used, terminals 3 and 4 on the
866 Indicating Circuit Module
can be jumpered together to
supply bell power from the
1912XR panel.
A maximum of 1 Amp at 12 VDC
is available from terminal 5 of
the 1912XR.
Auxiliary power supplies must be
regulated UL listed for Fire Protection
Signaling Service. Power supplies
must have battery backup.
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
AUXILIARY
POWER
SUPPLY
AUXILIARY
POWER
SUPPLY
10k EOL Resistor
DMP Model 308
BELL
4567
GND
REDB -
AC
AC
1
2
389
10
11
12
13
14 15
16
17 18 19
YEL GRN BLKB + SMK L5+ L5- L1 L2 L3 L4GNDGND
1k
3.3k Resistor
DMP Model 309
1k 1k
Dual Line Expansion
J10
Battery Only Restart
J16
Command Processor Reset
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
AUXILIARY
POWER
SUPPLY
24 VDC 5 Amp
Maximum
24 VDC 5 Amp
Maximum
You can have up to sixteen 866
Indicating Circuit Modules by using
the relay outputs available on the
1912XR panel.
All modules must be installed within
an approved enclosure connected
by conduit.
Zone 1 Indicating Circuit
Module. DMP Model 866
37mA at 12 VDC
Common
Indicating Circuit Module
DMP Model 866
37mA at 12 VDC
EPROM Socket
To additional Zone 1
Indicating Circuit Modules.
To additional Zone 2
indicating circuit modules.
Zone 1
Output
Zone 2
Output
Each 866 Indicating Circuit
Module in alarm draws up to
35mA from its terminal 3 alarm
input.
K5
K9
J15
Connects auxiliary
power to common
of Relay Output 1.
K9
Relay Output 1
Model 305 required.
K5
Relay Output 2
Model 305 required.
Relay Outputs 1 and 2
combined can provide
up to 600mA at 12 VDC
of panel auxiliary power.
Outputs 3 to 6 can
provide up to 50mA
each at 12 VDC. This
is sufficient for one
866 module per
indicating zone 3 to 6.
Relay 1
N/O
Orange
Relay 2
Common
Gray
Relay 2
N/O
Orange
Model 304
Output Harness
1k