XR500 Series Canadian Installation Guide Digital Monitoring Products
25
ComplianCe
False Alarm Reduction Programmable Options *
25.1 Shipping Defaults and Recommended Programming for ANSI/SIA CP-01-2010
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
DMP XR500
PROGRAMMING
GUIDE LT-0679
SECTION #
REQUIREMENT RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1ExitTime 15.2 Exit Delay
Required
(Programmable)
45sec.-250sec.
60
Seconds
60 Seconds
4.2.2.2Progress
Annunciation
15.2 Exit Delay Allowed
Individual keypads
may be disabled per
zone
All
keypads
enabled
All keypads enabled
4.2.2.3ExitTime
Restart
15.2 Exit Delay Required Option
For re-entry during
exit time
Enabled Enabled
4.2.2.5AutoStayArm
on Unvacated Premises
33.3 Occupied
Premise -
See XR500
InstallGuide(LT-0681)
Required Option
(except for
remote arming)
Area 1 = Perimeter
Area 2 = Interior
Enabled
Enabled for
Residential
Applications
4.2.4.4ExitTimeand
Progress Annunciation/
Disable - for Remote
Arm
Not Available on
Remote Arming
Allowed Option
Progress Annunciation
Always disabled for
Remote Arming
Not
Available
Remote Arming not
allowed for CP-01
installations.
4.2.3.1EntryDelay(s) 8.3 Entry Delay
Required
(Programmable)
30sec.–240Sec.**
30
Seconds
At least 30 Seconds **
4.2.5.1AbortWindow–
for Non-Fire Zones
3.7 Transmit Delay Required Option
Disable by zone or
zone type
Enabled
NT DY
EX Zone
Enabled
4.2.5.1AbortWindow
Time – for Non-Fire
Zones
3.7 Transmit Delay
Required
(Programmable
15sec.-45sec.**
30
Seconds
At least 15 Seconds **
4.2.5.1.2Abort
Annunciation
3.7 Transmit Delay Required Option
Annunciate that
no alarm was
transmitted(S45)
Yes Yes
4.2.5.4.1Cancel
Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that
a Cancel was
transmitted(S49)
Always
Enabled
Yes
4.2.6.1&4.2.6.2
Duress Feature
User Code + 1 =
Ambush Code Not
Available
Allowed Option
No 1 + derivative of
another user code/no
duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
4.3.1CrossZoning 16.22 Cross Zone Required Option
Yes/No Zone
Programming
No
Enabled using two or
more programmed
zones
4.3.1Programmable
Cross Zoning Time
8.4CrossZoneTime Allowed 4sec.-250sec. 4Seconds
Per walk path in
protected premises
4.3.2SwingerShutdown
8.7 Swinger Bypass
Trips
Required
(Programmable)
Forallnon-re
zones, shut down at
1 or 2 trips
One (1)
trip
One (1) trip
4.3.2SwingerShutdown
Disable
16.16 Swinger Bypass Allowed
For non-police
response zones
Yes Enabled (all zones)
4.3.3FireAlarm
Verication
16.4ZoneType Required Option FV Type Zone No
Yes as required
(unless sensors can
self verify)
4.5CallWaitingCancel
3.19 Telephone
Number
Required Option
Include *70P in
Telephone Number
Disabled
Enabled if user has
call waiting
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.