Digital Monitoring Products XR500 Series Canadian Installation Guide
26
ComplianCe
False Alarm Reduction Programmable Options (continued)
25.2 Call Waiting (ANSI/SIA CP-01-2010)
TheCallWaitingdefaultsettingisdisabled.TocanceltheCallWaitingfeature,program*(star)70P(pause),the
standardtelephonecodeprexthatcancelscallwaiting,intothetelephonenumberstring.CancelCallWaiting
fortelephonelinesthathaveCallWaitingoperationalonthetelephoneline.SeetheXR500SeriesCanadian
ProgrammingGuide(LT-0679CAN).
Caution: A call waiting cancel programmed on a non-call waiting telephone line, would prevent
communication to the central station.
25.3 Occupied Premise (ANSI/SIA CP-01-2010)
Whenonlytwoareasareused,andareaoneisnamedPerimeter,andareatwoisnamedInterior,andnoexittype
zone transition occurs during the exit delay because the premise continues to be occupied, the Interior area will
automatically disarm at the end of the exit delay.
25.4 Entry Delay (ANSI/SIA CP-01-2010)
OnlyuseEntryDelay1.DonotuseEntryDelay2,3,or4.SeetheXR500SeriesCanadianProgrammingGuide
(LT-0679CAN).
25.5 Minimum Installation Requirements (ANSI/SIA CP-01-2010)
SIA CP-01-2010 minimum system installation requirements include an XR500, a listed local Bell, and off premise
DACT communication to an SCS-1R receiver plus one of the following compatible keypads.
7060, 7063, 7070, or 7073 Thinline™ keypads
7060A, 7063A, 7070A, or 7073A Aqualite™ keypads
7160, 7163, 7170, or 7173 Thinline™ keypads