XR500 Series Programming Guide Digital Monitoring Products
27
SyStem OptiOnS
9.6
CRS ZONE TM: 4
Cross Zone Time
Enter the time allowed between zone faults. When zones are cross zoned, the same zone
or a second cross zoned zone must fault within this time in order for an alarm report for
both zones to be sent to the receiver. If the cross zone time expires without the second
zone faulting, only a zone fault from the rst zone is reported. Cross-zone time can be
from 4 to 250 seconds. Entering 0 (zero) disables this function. Default is 4. See the
Appendix.
9.7
RETARD DELAY: 10
Zone Retard Delay
Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, Auxiliary 2, Arming, and
Panic type zones. The retard delay only functions when the zone is shorted. The zone
must remain shorted for the entire length of the Retard Delay before being recognized
by the panel. The Zone Retard Delay can be from 1 to 250 seconds. Entering a 0 (zero)
disables this function.
9.8
PWR FAIL HRS: 1
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off for the
length of the programmed delay time, an AC power failure report is sent to the receiver.
The delay time can be from 1 to 15 hours. Entering a 0 (zero) sends the power failure
report after a 15-second delay. The default setting is 1.
Note: For UL burglary installations Power Fail Delay shall be programmed to 0 (zero).
Note: For UL re installations, Power Fail Delay shall be programmed as required
by the service of the panel. For Central Station service: 6-12, for Remote Station
service: 12-15.
9.9
SWGRBYPS TRIPS: 2
Swinger Bypass Trips
Enter the number of times (1-6) a zone can go into an alarm or trouble condition within
one hour be fore being auto matically bypassed. Bypassed zones are auto matically reset
when the area they are assigned to is disarmed. All 24-hour zones are reset when any
area of the system is dis armed. A programming Stop operation restores a bypassed zone.
Entering 0 (zero) disables this function. Default is 2.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires before
the trip counter is exceeded, the trip counter returns to 0 (zero). If the trip counter is
exceeded before the hour expires, the zone is auto matically bypassed by the panel. A
Bypass Re port is sent to the receiver if Bypass Re ports is YES.
Note: Not investigated by UL.
9.10
RST SBYP NO YES
Reset Swinger Bypass
When YES is selected, an auto matically bypassed zone is reset if it remains in a normal
condition for one complete hour after being bypassed. A report of the automatic reset is
sent to the receiver if Bypass Reports has been se lected as YES. Default is NO.
Note: Not investigated by UL.
9.11
TIME CHG NO YES
Time Zone Changes
This function allows the panel to request automatic time changes from the
DMP SCS-1R Receiver on Path 1. For the receiver to send time changes, it must be
programmed to send time changes and must be receiving time change updates from the
network automation computer at least every 24 hours. Default is YES.
HRS FROM GMT: 6
When time zone is programmed YES, enter the number (0-23) that indicates the
Greenwich Time zone (GMT) where the panel is located. The default is 6.