Vista de página 13
Digital Monitoring Products XR100 Series Installation Guide
6
INTRODUCTION
XR100 Series Installation Guide Digital Monitoring Products
7
INSTALLATION
3.4 Accessory Devices (continued)
Indicating and Initiating Devices
865 Supervised Style Y or Z
Notication Circuit Module
Provides supervised alarm current when using the XR100 Series panel bell output and up to
5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 865 can supervise
2-wire Style Y or Z circuits for ground faults, opens, shorts, and shorts with individual LED
annunciation.
866 Notication Circuit Module Provides supervised alarm current using the XR100 Series panel bell output and up to 5 Amps
at 12 or 24 VDC when using a listed auxiliary power supply. The 866 can supervise Style W
circuits for opens and shorts.
867 Style W LX-Bus Notication
Circuit Module
Provides supervised alarm current using the XR100 Series panel bell output and up to 5 Amps
at 12 or 24 VDC when using a listed auxiliary power supply. The 867 connects to the XR100
Series panel LX-Bus™ and provides one 2-wire Style W notication circuit for ground fault,
open, and short conditions. Individual Bell Relay addresses Bell Ring styles.
869 Dual Style D Initiating
Module
Provides two Style D, 4-wire initiating zones for connecting waterow switches and other
non-powered re and burglary devices.
Accessory Modules and Keypads
893A Dual Phone Line Module Allows you to supervise two standard phone lines connected to an XR100 Series panel. The
893A module monitors the main and backup phone lines for a sustained voltage drop and
alerts users when the phone line is bad.
* ePAD™ Virtual Keypads Allows users to control the security system from any computer in the world using the Internet.
LCD keypads Allows you to control the panel from various remote locations. Connect up to sixteen
supervised Model 630F Remote Fire Command Center, Model 690/690F, 790/790F Security
Command™ keypads, 693/793 Easy Entry™ keypads, 7060, 7063, 7070, 7073 Thinline™
keypads, 7060A, 7063A, 7070A, 7073A Aqualite™ keypads, or 7760 Clear Touch™ keypad to
the keypad bus using terminals 7, 8, 9, and 10.
Addressable Smoke Detectors
521LX, 521LXT Single-zone, addressable module conventional smoke/smoke heat detectors that connect to
the LX-Bus. Includes remote maintenance reporting, drift compensation, and multi-criteria
detection.
* This device has not been investigated by UL and shall not be used in UL installations.
3.5 Notication Appliances
The following table indicates the approved notication appliances that can be used with the XR100 Series system.
Wheelock Model No. Description 12V
MT-12/24 Multi-tone Horn x
NH-12/24 Standard Horn x
MB-G6-12 Bell, 6 inch x
MB-G10-12 Bell, 10 inch x
RSS-121575W-F Strobe, 15/75 candela x
RSSP-121575W-F Strobe, w/retrot plate x
NS-121575W-F Horn Strobe, 15/75 candela x
SM-12/24-R Sync Module, Single circuit, x
DSM-12/24-R Sync Module, Dual circuit x
Vista de página 13