Digital Monitoring Products XR100 Series Installation Guide
22
COMPLIANCE
XR100 Series Installation Guide Digital Monitoring Products
23
COMPLIANCE
22.4 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the XR100 Series Programming Guide
(LT-0896).
22.5 Proprietary Dialer
The Model XR100 Series provides Grade A proprietary service when congured as a digital dialer.
22.6 Grade B Central Station
Grade B Central Station service can be provided under by adding a Grade A Ademco AB12M bell and bell housing and
placing the Model XR100 Series panel into the Model 350A Grade A Attack Resistant Housing.
22.7 Bell Cutoff
The Bell Cutoff time cannot be less than 15 minutes. See the XR100 Series Programming Guide (LT-0896).
22.8 AA High Line Network Security
High Line Security is provided when congured as a NET system using an XR100N panel. The NET Check-in time
must be set from 01 to 06 minutes or AA. When programmed for UL AA (UL High Line Security) Exit Time Restart is
disabled. When a dialer is required for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A)
is required. When the check-in time is set to a number less than 200 seconds, an attack resistant enclosure is not
required. See sections 3.2, 3.2.1, and 3.3 of the XR100 Series Programming Guide (LT-0896).
The Model XR100 Series Protected Premises Control Unit is suitable for Grade AA service when congured for NET
communication with SCS-1/SCS-1R receiving system. This conguration is approved for the following:
AMCX - Central Station Alarm Units
APOU - Proprietary Alarm Units
UL 636 Specications
Holdup Alarm Units
23.1 UL 1610 Required
The programming and installation specications contained in this section must be completed in addition to UL 1610
Specications when installing a Model 1142 with a Model XR100 Series panel.
23.2 1100X Wireless Receiver
The Model 1100X Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be installed
in the system.
23.3 Wireless Supervision Time
The Zone Information Supervision Time must be a maximum of 60 minutes. See the XR100 Series Programming Guide
(LT-0896).
23.4 LED Display
The LED Operation option display must be set to NO when using a Model 1142 Holdup Alarm Transmitter. See the
XR100 Series Programming Guide (LT-0896).
23.5 Jamming Detection
The Detect Wireless Jamming option must be set to YES. See the XR100 Series Programming Guide (LT-0896).
23.6 Local Alarm
The Bell Action for a PN (Panic) type zone must be programmed as N (None). See the XR100 Series Programming
Guide (LT-0896).
23.7 Message to Transmit
The Armed Open and Armed Short messages for a PN (Panic) type zone must be programmed to A (Alarm). See the
XR100 Series Programming Guide (LT-0896).