XRSuper6/XR20/XR40 Installation Guide Digital Monitoring Products
17
ComplIanCe
ANSI/UL 365 Specications
Police Station Connected Systems
20.1 Entry Delay
The maximum entry delay must not exceed 60 seconds with the Model 350A housing. See LT-0305.
20.2 Bell
A local audible signal appliance must be used.
The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be
mounted on the outside of the building, visible from a public street or highway. It shall be accessible for
examination and repair. It shall also be located not more than four stories above the street level unless:
a) A second alarm sounding device and housing, intended for outside service, is mounted adjacent to the
premises or area of the building in which the alarm system is installed or
b) A second alarm sounding device, intended for inside service, is mounted within the premises.
In either case, the outside alarm sounding device and housing may be mounted as high as the seventh oor.
20.3 Bell Cutoff
The bell cutoff time cannot be less than 15 minutes. See the Programming Guide (LT-0305).
20.4 Automatic Bell Test
The Automatic Bell Test option must be programmed as YES. See the Programming Guide (LT-0305).
20.5 Mercantile
For Mercantile and Police Station Connect operation the XRSuper6/XR20/XR40 panel and all standby
batteries must be mounted in an attack resistant housing (DMP Model 350A).
20.6 Mercantile Safe and Vault
When the DMP Model 350A housing is used, the panel provides operation as a mercantile safe and vault
alarm. Bell Supervision and wiring must be in accordance with UL 681. If the panel is mounted outside the
safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should
be used. The XRSuper6/XR20/XR40 does not provide operation as a Bank Safe and vault alarm.
20.7 Line Security for Police Connect
Basic line security is provided when the Model XRSuper6/XR20/XR40 is congured as a dialer system.
20.8 Standard Line Network Security
Standard Line Security is provided when congured as a NET system using an XRSuper6, XR20, or XR40 panel
with an iCOMSL™ Network Alarm Router. The NET Check-in time must be set from 01 to 06 minutes. When a
dialer is required for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A) is required.
When the check-in time is set to a number less than 200 seconds (1, 2, or 3 minutes), an attack resistant
enclosure is not required. See the Communication section of the XRSuper6, XR20, XR40 Programming Guide
(LT-0305).
20.9 Wireless Arming Mode
The System Options Mode for arming must be programmed as Area or All/Perimeter (A/P). See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
20.10 Wireless Tamper
The Zone Information Disarmed Open Message to Transmit must be programmed Trouble (T). See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
20.11 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1103 must be programmed Normally Closed. See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
20.12 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero). See the XRSuper6, XR20, XR40
Programming Guide (LT-0305).
20.13 Wireless Audible Annunciation
The Wireless Audible option must be selected as ANY for commercial applications.