16.5 Using the 984 Command Function
This feature allows
the integrity of the cellular communication to be tested.
NBR:
Not available for XTL/XTLC panels. If selected the keypad displays NO DIALER.
TEST: This option tests each function of the panel’s cellular communication. The tests proceed until a function
does not pass, or until all have been tested with positive results. The progress displays during each test.
PICKUP: Not available for XTL/XTLC panels. If selected the keypad displays NO DIALER.
16.6 Using the Walk Test
The XTL/XTLC panel provides a walk test feature that allows a single technician to test all the protection
devices connected to zones on the system. Conduct the Walk Test within 30 minutes of resetting the panel. The
Walk Test automatically ends if no zones are tripped for 20 minutes. TEST IN PROGRESS displays at all keypads.
When ve minutes remain, TEST END WARNING displays. If any areas are armed the Walk Test does not start
and SYSTEM ARMED displays.
Walk Test
To conduct the Walk Test, reset the control panel by pressing the reset button then wait
one minute. From the keypad, enter the code 8144. The keypad displays WALK TEST.
WLS (Wireless Check-in Test) - Select WLS to automatically test 1100 Series wireless
transmitter communications. Includes all wireless devices except key fobs and
transmitters programmed for a supervision time of 0 (zero).
PIR (Wireless PIR Walk Test) - The PIR Walk Test allows the installer to verify the 1126 and
1127 operation. When enabled, the 1126 LED ashes each time motion is detected for up to
30 minutes. This is a local test only and no messages are sent to the Central Station.
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a supervisory
check-in message.
•The number of zones that check in. (XX in the example).
•The total number of wireless zones programmed for supervision that should check in.
(ZZ in the example).
END - Select END to stop the Wireless Check-in Test. When the test ends or a 20-minute
time-out expires, normal wireless zone processing returns. If all transmitters check-in,
both numbers will match within three (3) minutes. If a transmitter has multiple zones
(1101, 1114, etc.), all zones will be included in the counts. Failed wireless zones then
display on the keypad.
Test End Warning
When no zones have been tripped and ve minutes remain on the 20 minute Walk Test
timer, the keypad displays TEST END WARNING and the keypad tones. If no additional test
zone trips occur, the test ends and a nal Sensor Reset automatically occurs. The System
Test End message is sent to the receiver along with Verify and Fail messages for each zone
under WALK test. Faulted zones then display on the keypad.
Failed Zones Display
Each zone that did not trip at least once during the Walk Test displays on the keypad that
initiated the test. Any Fire (FI) Panic (PN) or Supervisory (SV) 24-hour zone that is faulted at
the end of the Walk Test displays a trouble condition for that zone regardless of the message
programmed for the open or short condition of the zone and a zone trouble is sent to the
receiver. Press the COMMAND key to display the next failed zone.
For the Wireless Check-in Test, failed wireless zones display only on the keypad. Zone
Verify/Fail reports are not sent to the central station receiver for the wireless checkin
test.
WALK TEST
STD WLS PIR
WALK TEST
TRIPS: XXX END
TEST END WARNING
SOUTH LOBBY
ZONE: 10 -FAIL