XRSuper6/XR20/XR40 Programming Guide Digital Monitoring Products
21
ouTPuT oPTionS
8.7
ENTRY OUT: 0
Entry Output
This output turns on at the start of the entry delay time. The output turns off when
the area disarms or the entry delay time expires. Enter 0 (zero) to disable.
8.8
EXIT OUT: 0
Exit Output
This output turns on any time an exit delay time starts. The output turns off when
the system arms or when the arming has been stopped. Enter 0 (zero) to disable.
8.9
READY OUT: 0
Ready Output
This output turns on whenever all disarmed zones are in a normal state. The output
turns off when any disarmed zone is in a bad state. Enter 0 (zero) to disable.
8.10
ARMED OUT: 0
Armed Output
This output turns on when any time an area of the system arms. The output turns
off when the system completely disarms. Enter 0 (zero) to disable this output.
8.11
BURGLARY OUT: 0
Burglary Output
This output turns on any time a burglary zone goes into alarm. The output turns off
when the area in which the alarm occurred disarms and no other burglary zones are
in alarm. Enter 0 (zero) to disable this output.
8.12
GND STRT OUT: 0
Ground Start Output
This output is turned on for 750ms any time the panel seizes the telephone line.
Enter 0 (zero) to disable this output.
Note: Ground Start Output is not compatible with outputs 31-34 and 41-44.
8.13
CELL BKP OUT: 0
Cellular Backup Output
When connected to a double pole, double throw relay, this output allows cellular
communication with the Cell-Miser restrictions listed below. The panel’s telephone
connection, the incoming telephone line, and the cellular telephone should be
connected to the relay to allow the panel’s telephone connection to be switched
between the incoming telephone and cellular. Enter zero to disable this output.
Note: Cellular Backup Output is not compatible with outputs 31-34 and 41-44.
1. Only zone alarms, Ambush, or Abort messages are sent over the cellular
system. Delayed Events are sent if the cellular call was made because of an
alarm, ambush or abort.
2. The second phone number is only used when the output is ON and should
contain numbers for a cellular call. This allows the panel to use the cellular
phone number for cellular calls only without needing prexes or area codes
for land-line dialing.
Attempt Cell Backup Output Phone Number
1 Off First
2 Off First
3 On Second
4 On Second
5 Off First
6 Off First
7 On Second
8 On Second
9 Off First
10 Off First
3. The rst phone number is always used when this output is off.
4. When a message is sent that is not a Cell-Miser message, such as O/C and
troubles, the output does not turn ON and only the rst telephone number is
used for all ten attempts.
Note: When an output is chosen for Cellular Backup, the Backup Reporting option in
Receiver 1 and 2 programming will automatically be set to NO.