Digital Monitoring Products XR150/XR350/XR550 Series Programming Guide
12
NETWORK OPTIONS
Network Options (Network or Encryption Only)
Network Options are provided to dene the network conguration for the panel. This information will be used
during communication of messages via network.
Note: IP addresses and port numbers may need to be assigned by the network administrator. When entering an IP,
Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods. For example, IP address
192.168.000.250 is entered as 192168000250.
4.1 DHCP Mode Enabled
If the panel uses a dynamic IP address select YES. When set to YES, the panel operates
using DHCP and does not use the Local IP Address number. When the DHCP option is set to
NO, the panel uses the IP address entered in Local IP Address. The default value for DHCP
mode is YES.
4.2 Local IP Address
Enter the local IP address. The Local IP Address must be unique and cannot be duplicated.
The default local IP address is 192.168.0.250.
4.3 Gateway Address
Enter the local gateway address. The Gateway IP Address is needed to exit your local
network. The default gateway address is 192.168.0.1.
4.4 Subnet Mask
Enter the local subnet mask assigned to the panel. The default subnet mask address is
255.255.255.000.
4.5 DNS Server
Enter the IP address of the DNS (Domain Name System) used by the panel to resolve domain
names into IP addresses. The default address is 192.168.0.1.
4.6 Passphrase (XR550 with Encryption only)
To enable encryption type an 8 to 16-character Passphrase using alphanumeric characters.
If you leave the Passphrase blank, the panel communicates with the SCS-1R Receiver, but
the data is not encrypted. The Passphrase is blank by default.
An XR550 panel with encryption is capable of communicating 128-bit or 256-bit encrypted
data to an SCS-104 line card installed at the receiver. The XR550 panel with encryption and
the receiver SCS-104 line card must have the same password called a Passphrase.
Note: DO NOT LOSE THE PASSPHRASE. A lost or forgotten Passphrase requires that the XR550
panel and every SCS-104 line card at the receiver be individually reprogrammed with a new
passphrase.
Note: An XR550 panel with encryption communicates using AES encryption. If you currently
have an XR550 panel with network installed, you may purchase a separate feature key to
activate encrypted communications using the Feature Upgrade process described in the
Feature Upgrade Section. Encrypted communication cannot be enabled on a standard
XR550 panel.
Note: 256-bit encrypted messages to the SCS-1R receiver only communicate when using
SCS-104 Receiver Line Cards with Version 102 or higher software.
4.7 734N Listen Port.
Enter the port number that the 734N/734N-WiFi will use to send communication to
the panel. This must be the same port that is programmed in Panel IP Port within the
734N/734N-WiFi Communication programming menu.
Note: The 734N Listen Port cannot be the same as the panel network programming port.
4.8 734N Passphrase
Enter an 8 to 16-character Passphrase to encrypt communication with the
734N/734N-WiFi module. The 734N Passphrase must match the 734N Passphrase entered in
Communication programming of the 734N. The Passphrase is blank by default.
Note: A passphrase is required for operation.
DHCP NO YES
LOCAL IP ADDRESS
192.168.0.250
GATEWAY ADDRESS
192.168.0.1
SUBNET MASK
255.255.255.000
DNS SERVER
192.168.0.1
PASSPHRASE
-
734N LISTEN
PORT: 2002
734N PASSPHRASE
-