XR150/XR350/XR550 Series Programming Guide Digital Monitoring Products
59
APPENDIX
Note: During the Walk Test, trip each zone device or button on the system for 1 to 2
seconds. You do NOT have to hold the zones for 2 seconds in normal mode for PN type
zones. You are only required to hold the panic during the Walk Test because the zone takes
additional time to report when the system is in test mode.
WLS PIR
WLS (Wireless Check-in Test) - Select WLS to automatically test wireless transmitter
communications. Includes all wireless devices except key fobs and transmitters
programmed for a supervision time of 0 (zero).
PIR (Wireless PIR Walk Test) - The PIR Walk Test allows the installer to verify the 1126 or
1127 operation. When enabled, the PIR LED ashes each time motion is detected for up to
30 minutes. This is a local test only and no messages are sent to the Central Station.
BELL NO YES PULS
Bell Action
This option selects the bell output action when a zone under test faults. This option allows
the panel bell, and/or burglary bell, and/or re bell to turn ON and then OFF each time a
zone is tripped (opened or shorted).
NO - Select NO for no bell output action during Walk Test.
YES - Select YES to turn on any bell output for 2 seconds during Walk Test.
PULS - Select PULS to turn on any bell output for 1/4 second during Walk Test. Any LX-Bus
device output turns on for 1.6 seconds due to the polling cycle.
Trip Counter For Walk Test
Once in the Walk Test, walk around and trip each protective device. Continue tripping
devices until the entire system is tested.
With each zone trip during the Walk Test:
Keypad display increments each time a selected zone is opened or shorted
The keypad buzzes for two seconds
The panel sounds the alarm bells as programmed in Bell Action
Each time a FI, FV, or SV zone trips, a Sensor Reset occurs.
If ENHANCED ZONE TEST is selected as YES:
A Verify message is sent at the time the zone trip occurs instead of at the end of the Walk
Test. For FI, FV or SV zone types, the Verify message is sent at the initial trip.
For all other zone types, the Verify message is sent when the zone restores. This allows the
Central Station to count the number of devices per zone.
END - Select END to stop the Walk Test. When the Walk Test ends or a 20-minute time-out
expires, a nal Sensor Reset occurs. The System Test End message is sent to the receiver
along with Verify and Fail messages for each zone under test. Faulted zones then display on
the keypad.
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a supervision check-
in message.
• The number of zones that check in. (XXX in the example).
The total number of wireless zones programmed for supervision that should check in.
(ZZZ in the example).
END -
Select END to stop the Wireless Check-in Test. When the test ends or a 20-minute
time-out expires, normal wireless zone processing returns. If all transmitters check-in, both
numbers match within three (3) minutes. If a transmitter has multiple zones (1101, 1114,
etc.), all zones are included in the counts. Failed wireless zones display on the keypad.
Test End Warning
When ve minutes remain on the 20 minute Walk Test timer, the keypad displays TEST
END WARNING. If no additional test zone trips occur, the test ends and a nal Sensor Reset
automatically occurs. The System Test End message is sent to the receiver along with
Verify and Fail messages for each zone under Walk Test. Faulted zones then display on the
keypad.
Note: Key fobs do not send failure messages in order to prevent functioning key fobs that
are not present at the time of the test from being reported as MISSING.
TRIPS: XXX END