XR150/XR350/XR550 Series Programming Guide Digital Monitoring Products
29
BELL OPTIONS
Bell Options
10.1 Bell Options
This section allows you to program the panel bell output functions.
10.2 Bell Cutoff Time
Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the area is
disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell output. The
default is 15 minutes.
Note: To support the Alarm Verify feature on an All/Perimeter or Home/Sleep/Away
system, set the Bell Cutoff Time to greater than 0.
10.3 Automatic Bell Test
Select YES to turn on the Bell Output for 2 seconds each time the system is com pletely
armed from a keypad. This test is delayed until the Closing Wait acknowledge is received
(if programmed). If the Closing Wait acknowledge is not received within 90 seconds, the
bell test does not occur. Arming performed from an Arming zone or from Remote Link™ does
not activate the Bell Test.
10.4 Bell Output
Enter the output/Favorite number when needed to follow the panel Bell Output operation
for all action and off conditions. Enter 0 (zero) to disable.
Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action for an LX-
Bus output is pulse.
Note: Bell Output should not be programmed for a Model 1135 Wireless Siren when
programmed in Output Information to Trip with Panel Bell.
10.5 Bell Action
This section denes the type of Bell Output for zone alarms. Press COMMAND to display the
default Bell Output for each zone type. Press any Select key and enter S for a Steady Bell
Output, P for a Pulsed output, T for a Temporal Code 3 output, and N for no Bell Output.
Note: Trouble conditions do not activate the Bell Output.
10.5.1 Fire Bell Action
Denes Bell Action for Fire Type zones. The default is P.
10.5.2 Burglary Bell Action
Denes Bell Action for Burglary Type zones and Exit Error output. The default is S.
10.5.3 Supervisory Bell Action
Denes Bell Action for Supervisory Type zones. The default is N.
10.5.4 Panic Bell Action
Denes Bell Action for Panic Type zones. The default is N.
10.5.5 Emergency Bell Action
Denes Bell Action for Emergency Type zones. The default is N.
10.5.6 Auxiliary 1 Bell Action
Denes Bell Action for Auxiliary 1 Type zones. The default is N.
10.5.7 Auxiliary 2 Bell Action
Denes Bell Action for Auxiliary 2 Type zones. The default is N.
BELL OPTIONS
BELL CUTOFF: 15
BELL TST NO YES
BELL OUTPUT: 0
BELL ACTION . . . . .
FIRE TYPE: P
BURGLARY TYPE: S
SUPRVSRY TYPE: N
PANIC TYPE: N
EMERGNCY TYPE: N
AUXLRY 1 TYPE: N
AUXLRY 2 TYPE: N