Digital Monitoring Products XR150/XR350/XR550 Series Programming Guide
44
ZONE INFORMATION
18.4 Zone Type
The Zone Type denes the panel response to the zone being opened or shorted. This is
called the Alarm Action. There are up to 13 possible alarm action responses depending on
the zone type and any restrictions it may have. See the Zone Type chart in the Appendix.
When you assign a Zone Type to a zone, automatic zone responses are made. There are 12
Zone Types to choose from. Application descriptions for each zone type can be found in the
Appendix of this manual.
To enter a new Zone Type, press any Select key. The display lists all of the available
Zone Types four at a time.
Blank, Night, Day, or Exit. Press COMMAND for additional zone types.
Fire, Panic, Emergency, or Supervisory. Press COMMAND for additional zone types.
Auxiliary 1, Auxiliary 2, Fire Verify, or Arming (keyswitch). Press COMMAND for additional
zone types.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone
Type, the zone must be assigned to an active area. If you select Fire, Fire Verify, Panic,
Emergency, or Supervisory as the Zone Type, it is a 24-hour zone that is always armed and
no area assignment is needed.
Zone Type Specications
The panel contains 12 default zone types for use in conguring the system. These zone
types provide the most commonly selected functions for their applications. All zone types
except the Arming zone type can be customized by changing the options listed below.
Arming zone type programming continues at Arming Zone Area Assignment.
Refer to the Appendix for complete zone type descriptions.
18.5 Area Assignment
Enter the area number where the Night, Day, Exit, Auxiliary 1, or Auxiliary 2 zone is being
assigned. For an Area system, area numbers 1-32 can be assigned. For a Home/Sleep/Away
with Guest system, area numbers 1-9 can be assigned.
In an All/Perimeter or Home/Sleep/Away system, the currently selected area, Perimeter,
Interior, Bedroom displays.
On an All/Perimeter system, select INT to program zones for the interior area and select
PERIM to program zones for the perimeter area.
On a Home/Sleep/Away system, select INT to program zones for the interior area, select
BDRM to program zones for the bedroom area, and select PERIM to program zones for the
perimeter area.
18.6 Fire Bell Output
This output (1 to 6, 500 to 999, F1 to F20, G1 to G20, or D1 to D16) is turned on any time a
Fire, Fire Verify, or Supervisory zone is placed in alarm. The output is turned off by any the
following actions:
• When the User Menu Alarm Silence function is performed.
• When a valid user code is entered to silence the bell.
• When the Silence key is pressed on the 630F Remote Fire Command Center.
• Using the Outputs On/Off function in the User Menu.
• The expiration of the Bell Cutoff time.
This output can be connected to a lamp, LED, or buzzer using the DMP Model 716 Output
Expansion Module.
18.7 Arming Zone Area Assignment
In an Area or Home/Sleep/Away with Guest system, if the zone has been programmed as an
Arming Type (AR), enter the areas that the zone controls.
When the zone changes from normal to shorted, the programmed areas toggle between the
armed or disarmed condition using the Style programming below. When restored to normal,
no action occurs. When the zone is opened from a normal (disarmed) state, a trouble is
reported. When opened from a shorted (armed) state, an alarm is reported and the zone is
disabled until you disarm the area(s) from either a keypad or Remote Link™ computer.
ZONE TYPE: BLANK
- - NT DY EX
FI PN EM SV
A1 A2 FV AR
AREA NO: -
AREA: PERIMETER
INT PERIM
INT BDRM PERIM
FIRE BELL OUT: 0
ARM/DIS AREAS